With this tool, you can view and edit the values for the writeLevels/priorities.
How to use BACnet Priority Array
- Expand the Equip Tree and select a BACnet point that is writable.
- Click Tools .
- The Tools dialog box displays.
- In the Tools dialog box, select BACnet Priority Array.
- The BACnet Priority Array dialog box displays.
- In the BACnet Priority Array dialog box, select the value for any priority and writeLevel, and then click Edit.
- The Change BACnet Priority Array dialog box displays.
- Set the desired value, click Next and then click OK.