2-pipe fan coil unit - Basic Documentation - RDF302 - RDF302.B - RDF302/VB

Semi-flush mount room thermostats with RS485 Modbus communications RDF302, RDF302.B, RDF302/VB

Product Family
Product Group
Thermostats (temperature controller with sensor)
Content Language
English
Content Type
Technical Documentation > Basic Documentation
Product Version
Status
Valid
Date
2022-06-17
Document No
CE1P3079en
Download ID
A6V10350339
Stock No.
S55770-T238
S55770-T416
S55770-T428
Product No.
RDF302
RDF302.B
RDF302/VB

On 2-pipe applications, the thermostat controls a valve in heating / cooling mode with changeover (automatically or manually), heating only, or cooling only. Cooling only is factory-set (P01 = 1).

ON/OFF control

Control sequence
ON/OFF output

The diagrams below show the control sequence for 2-position control.

Heating mode Cooling mode
T[°C] Room temperature SDH Switching differential “Heating” (P30)
w Room temperature setpoint SDC Switching differential “Cooling” (P31)
V1 Control command “Valve” or “Compressor”

Modulating control: 3-position

Control sequence modulating output

The diagrams below show the control sequence for modulating PI control.

Heating mode Cooling mode
T[°C] Room temperature XpH Proportional band “Heating” (P30)
w Room temperature setpoint XpC Proportional band “Cooling” (P31)
V1 Control command “Valve”

Note:

The diagrams only show the PI thermostat’s proportional part.

Setting the sequence and the control outputs

Refer to sections 3.4 "Applications", 3.6.1 "Sequences", and 3.7 "Outputs".