Integration via Modbus - Basic Documentation - RDF302 - RDF302.B - RDF302/VB

Semi-flush mount room thermostats with RS485 Modbus communications RDF302, RDF302.B, RDF302/VB

Product Family
Product Group
Thermostats (temperature controller with sensor)
Content Language
English
Content Type
Technical Documentation > Basic Documentation
Product Version
Status
Valid
Date
2022-06-17
Document No
CE1P3079en
Download ID
A6V10350339
Stock No.
S55770-T238
S55770-T416
S55770-T428
Product No.
RDF302
RDF302.B
RDF302/VB

The RDF302, RDF302/VB and RDF302.B are communicative thermostat with Modbus open protocol on RTU (Remote Terminal Unit) mode enabling easy integration into BACS via RS-485.

The following Modbus functions are available:

  • Central controls of room operating modes, setpoints, fan speed and fan mode

  • Remote monitoring e.g. operating mode, control outputs, temperature sensor or switch, etc.

  • Alarming, e.g. external fault contact, condensation, clean filter, etc.

  • Outside temperature or time of day via bus displayed on thermostat

  • Key lock

Engineering and commissioning can be done using…

– local DIP switches / HMI

– via Modbus commissioning tool