The alarm description for an automatically generated alarm type must always be modified. The alarm description always starts with the text Define the description text for Alarm ID: 8704. The customer does not understand it and it needs to be edited.
- The Alarm type view is open.
- Select Filter by.
- Select column header Alarm description and enter the automatically generated text Define the description text.
- Press <Enter>.
- The Alarm type list is filtered.
- Select automatically generated alarm type.
- Select
.
- Select Edit.
- The Alarm type dialog box opens.
- Change the designation in the Alarm description field.
- Enter the label name in the Alarm label field.
- Select Save.
- The edited alarm type is saved.