Only one alarm ticket is active for each device. The alarm ticket remains active until the user deletes it. No new alarm ticket is generated when an alarm is resolved but returns , before the alarm ticket is deleted. This prevents an alarm burst or flashing alarm from triggering multiple alarms.
Standard: Alarm response |
Flashing alarm: Additional incoming alarms do not trigger a new alarm ticket. |
Repeating alarm: An alarm is no longer pending before the alarm ticket is closed. |
Repeating alarm: An alarm is still pending , before the alarm ticket is closed. |
Alarm burst: Only one alarm ticket is generated for all alarms. A repeating alarm does not trigger a new alarm ticket. |