- Select the device to connect to the Cloud.
- Select the AS tab and then Cloud.
- Select Enable Cloud.
- Enter the other parameters for the connection.
Settings | Description |
---|---|
Enable Cloud | Select the BACnet property Enable connectivity to enable the Cloud port. |
Enable BACnet tunnel | Select the BACnet property Enable BACnet tunnel to enable BACnet tunneling. |
Reconnect delay | Enter the delay time to reconnect in seconds. |
Retries | Enter the numbered of retries to connect to a Cloud object if the connection is lost. |
Network Number | Read only. BACnet property that displays the BACnet network number. |
Registration URI | Read only. BACnet property that includes the Cloud registration URI. The Cloud agent uses it to register the device in the Cloud. |
Activation key | The key is visible after initial readback. |