The selected application and its parameters as well as input and output configuration determine the room automation station's functionality.
A detailed description of functionality is available in the ABT (Automation Building Tool) online help.
Communication
- BACnet MS/TP
- USB connection for service and commissioning, firmware download, and LAN access.
- The following functions are available with the KNX PL-Link bus:
- Communication with room operator units, switches, sensors, actuators, and luminaires.
- Plug-and-play connection of Siemens field devices with KNX PL-Link.
LED indication
LED |
Color |
Activity |
Function |
---|---|---|---|
RUN |
Green |
Steady ON |
Device is ready for operation |
Steady OFF |
Device is not powered | ||
Regular flashing |
Start-up or the program is stopped | ||
Red |
Steady OFF |
OK | |
Steady ON |
Program error | ||
Rapid flashing |
Wrong or corrupt software | ||
Blinking per wink command |
Physical device identification | ||
|
Service button (SVC)
Physical identification on the network.