Upon insertion of the detector, the detector base is stressed by compression, tension and torsion. The fixing must thus be designed accordingly.
Detector bases must be placed flat on the ceiling.
Avoid mounting on steps, concrete ribs, etc.
When selecting the installation position, take into account any structures that may impair radio reception.
There must be at least 50 cm of free space below and at least 2 cm to the sides of the detector, so that the detector can be removed with the detector exchanger.
Contorted detector bases complicate or even impede the insertion of the detectors with the detector exchanger.