Refer to the installation instructions for details.
WARNING
No changes permitted
No product modifications permitted.
Pre-mounting:
- Check that the hose, threads and seals are in good condition.
- Check that a seal is fitted on each thread.
- Never use a faulty hose.
To mount the hose:
- Remove the end caps.
- Screw up fully the swivel nut on the fitting using a 32 mm open-end wrench.
Torque: 55 Nm (±5 Nm).
- Apply tightening torques as specified.
- Do not bend the hose below the specified minimum radius.
- Make sure that no forces (traction, shear or twisting) are applied to the hose.