Auto-zero
The auto-zero sequence can be initiated by any of the following:
- Commanding BACnet object properties
- Configured time delay
- APS power on or return from power loss
The auto-zero sequence automatically adjusts the internal offset for the differential pressure sensor.
Reliability states
The APS reports all reliability states to the DXR2, including:
- BAD_CALIBRATION
- BAD_TRANSDUCER
- LOW_PRESSURE
- HIGH_PRESSURE
- CAL_IN_PROGRESS
- RESET_OCCURED
- BAD/NO COMM
- COMMUNICATION_FAILURE
LED Indication
Air sensor calibration blink pattern takes precedence over the communication blink pattern.
LED State | Status |
|---|---|
Green – solid | Running, no communication |
Green – blink 80/20 | Running, communication ok |
Green – blink 50/50 | Air sensor calibration mode |
Red – solid | Error condition |