Preparing the detector exchanger and tester
- The Bluetooth extension kit is installed in the detector exchanger and tester. You will find more information in document A6V10405496.
- Firmware version 3.2.8 or higher is installed on the detector exchanger and tester. You will find more information in document 007227.
- Switch the detector exchanger and tester on.
- If the symbol is not shown on the display, execute command '8.2 Enable'.
- Menu point '8.2 Disable' and the symbol are shown on the display.
- Execute the '8.1 Make visible' command.
- The text 'Device is visible as FDUD29x-XX-XX-XX' is shown on the display.
- The Bluetooth extension kit is switched on and visible to other devices.
1 | The last 6 numbers of the MAC number for the Bluetooth extension kit. |
Connecting the smartphone to the detector exchanger and tester
If the smartphone is already connected to a detector exchanger and tester, in certain circumstances, this may cause the connection to another detector exchanger and tester to fail via the settings of the 'Sinteso Test' app. Connect the other detector exchanger and tester directly using the native Bluetooth function of your smartphone if this occurs.
- The detector exchanger and tester is switched on and the symbol is shown on the display.
- The Bluetooth extension kit is visible to other devices.
- Switch on the Bluetooth function on the smartphone.
- Start searching for other visible Bluetooth devices from the smartphone.
- The smartphone searches for visible Bluetooth devices.
- A list of visible Bluetooth devices is displayed on the smartphone.
- Select the required 'FDUD29x-XX-XX-XX' in the list and accept the pairing.
- Open the 'Sinteso Test' app.
- Press and select 'Settings'.
- The 'Settings' view is displayed.
- Press 'Bluetooth'.
- The 'Sinteso Test' Bluetooth function is switched on.
- Press 'Tester Selection'.
- The visible Bluetooth devices are displayed.
- Click on 'FDUD29x'.
- 'Sinteso Test' establishes a connection to the Bluetooth extension kit.
- The symbol is shown on the detector exchanger and tester display.
- The detector exchanger and tester is not visible to Bluetooth devices with which a connection has not previously been established.