When alarm suppression is enabled for an object or subtree, depending on the alarm class you want to suppress, any events coming from those objects are suppressed. This means that any events relating to those objects do not display in the Summary bar and Event List of your Flex Client application, while all consequences of such events are not activated. However, value and status changes of the affected objects are still updated and logged in the history.
You can check whether the alarm suppression is Enabled
or Disabled
for an object in the Properties tab. You can also enable or disable alarm suppression, and filter System Browser to display those system objects:
- When this feature is enabled for a specific object/subtree, it will activate on the next events that occur. Any events detected prior to enabling this feature will remain in the Summary bar and Event List of your Flex Client application.
- When this feature is disabled for a specific object/subtree, any detected events relevant to that object/subtree display immediately in the Summary bar and Event List of your Flex Client application.
NOTE: Enabling and disabling alarm suppression is carried out from the Properties tab, either in the System or Event context. The following procedures describes the Events context only.
Prerequisites:
- You are authorized to handle alarm suppression.
- One or multiple system objects support the alarm suppression feature.
Block Alarm Transmission to Fire Department
The alarm suppression feature disables the display of events concerning the affected object or subtree. The alarm functionality (for example, the fire detection system) is not affected. Consequently, any incoming alarms are still transmitted to the fire department.
To block the alarm transmission to the fire department, you must exclude the fire detection by disabling the area, zone, or fire detector on the panel as follows:
- In Event List, select the event for the fire object to be changed.
- In the pane on the right, select the Properties tab.
- The object properties displays on the right.
- Next to the Mode property, select and then Disable.
- Select .
Enable Alarm Suppression for a Single Object
- In Event List, select the event for the object to be changed.
- In the pane on the right, select the Properties tab.
- If necessary, switch Basic to Advanced.
- The object properties displays on the right.
The Alarm Suppression property indicates whether the alarm suppression isEnabled
orDisabled
for the selected object.
- Next to the Alarm Suppression property, select and then Enable.
- To suppress alarm classes for the selected single object, from the Enable For drop-down list select one of the following:
- Select All classes to suppress all the events on the management station.
- Select a specific alarm class whose events you want to suppress on the management station.
- Alarm suppression is enabled for the selected single object. By default, if the selected single object is in alarm when you enable alarm suppression its events remain visible in the Summary bar and Event List. Alarm suppression will activate on the next events that occur.
NOTE: The following error message displays if the alarm suppression feature is not available for your configuration:Enable failed
.
- Select .
- The alarm suppression updates accordingly for the relevant single object.
NOTE: The following error message displays if the alarm suppression feature is not available for your configuration:Alarm Suppression command execution failed!
Enable Alarm Suppression for an Entire Subtree
- In Event List, select the subtree to be changed to be changed.
- In the pane on the right, select the Properties tab.
- The subtree properties displays on the right.
The Alarm Suppression property indicates whether the alarm suppression isEnabled
orDisabled
for an entire subtree (that is, for the selected object and all objects below the selected object in the tree).
- Next to the Alarm Suppression property, select and then Enable All.
- To suppress alarm classes for the selected subtree, from the Enable For drop-down list select one of the following:
- Select All classes to suppress all the events on the management station.
- Select a specific alarm class whose events you want to suppress on the management station.
- Alarm suppression is enabled for the selected subtree. By default, if the selected object or any object below the selected object in the tree is in alarm when you enable alarm suppression, its events remain visible in the Summary bar and Event List. Alarm suppression will activate on the next events that occur.
NOTE: The following error message displays if the alarm suppression feature is not available for your configuration:Enable failed
.
- Select .
- The alarm suppression updates accordingly for the relevant object and all objects below the selected object in the tree.
NOTE: The following error message displays if the alarm suppression feature is not available for your configuration:Alarm Suppression command execution failed!
Disable Alarm Suppression
- In Event List, select the event for the object or subtree to be changed.
- In the pane on the right, select the Properties tab. The Alarm Suppression property indicates whether the alarm suppression is
Enabled
orDisabled
for the selected single object or for the selected object and any object below the selected object in the tree.
- Next to the Alarm Suppression property, select and then on of the following:
- Disable for the selected single object
- Disable All for the selected subtree
- Select .
- Alarm suppression is disabled for the selected single object or for the selected object and any object below the selected object in the tree.
Filter Objects Affected by the Alarm Suppression
- In the horizontal navigation bar, select System.
- In System Browser, select .
- Expand State.
- Select the Alarm Suppression check box.
- Select .
- The results display in System Browser.