The planning phase uses the floor plans to find preliminary installation points for TBRs/TMEs.

Generic simplified schema

Real floorplan

Wireless planning with generic simplified scheme and real floor plan

Draw a grid with horizontal and vertical lines at a distance of 30 m to the preliminary TME and TBR locations, starting in the top left corner of the floor plan. Start the grid 15 m from the building walls and continue to draw a grid of 30 m x 30 m squares.

Floorplan with initial planning grid

Review the floor plan and identify any possible obstacles, e.g. elevator shafts, concrete walls, vending machines, staircases, etc.. Mark any large obstacles on the floor plan.

Floorplan with highlighted obstacles

Decide in advance where to install TBR or TME devices. Note the device locations and type on the floor plan.

Floor plan with defined TBR and TME locations

Starting position for grid

Planning grid

Possible position of TBR/TME

Obstacle area

TBR

TME

SED