You can view Building X Connector properties and states in the Extended Operation tab by selecting Project> Management System > Servers > Main Server > Building X Connector.
Property | States |
Operational State | Not Ready: Not operational Ready: Operational Configuring: Retrieving current Building X configuration Registering: Registering Building X application Stopping: Transitioning to Not Ready |
Communication State | Fault: Coincides with Operational State ‘Not Ready’ Disconnected: The Building X Connector is not communicating with the Building Connect Agent Disconnecting: The Building X Connector is in the process of terminating communication with the Building Connect Agent Connecting: The Building X Connector is in the process of initiating communication with the Building Connect Agent Connected: The Building X Connector is communicating with the Building Connect Agent |
Building X Data State | Not Available: Coincides with Operational State ‘Not Ready’ Download Pending: Awaiting configuration download from Building X Download in Progress: Downloading configuration from Building X Download Failed: The Building X configuration is not aligned with the management station configuration (discovery or upload required) OK: Normal |
Discovery State | No Data: Discovery operation has not been executed Discovery In Progress: Discovery operation in progress Changes Detected: Discovered Desigo CC configuration differs from the current Building X configuration (upload required) Upload In Progress: Discovered configuration being uploaded to Building X No Changes: Discovered configuration matched Building X configuration |
Indications State | Disabled: Alarms and values will not be sent to Building X Enable: Alarms and values will be sent to Building X |