At low voltage the DS11i line is started as an FDnet line. This allows the topology to be determined.
Where DS11i devices are subject to a separator, the low line voltage prevents closure of the separator. That means that FDnet devices located behind such a DS11i device will not be found.
Use this function to test whether a DS11i line includes further DS11i devices that are subject to a separator.
- Reading in the line with the 'DS11i Migration: Start Mixed Line Scan’ function.
- Save the topology.
- Reading in the line with the 'DS11i Migration: Start Low Voltage Scan’ function.
- If the two topologies are compared, all remaining DS11i devices are localized.