Switch View
When a line card is read in via an FS20, this function allows the view to be switched to another connection of the same line card. This is not read in again. This is useful only for the following functions.
Start all connections
All connections are read in one after another. Nevertheless only the topology of one individual connection is displayed (and saved, exported etc.). See also 'Switch View'.
This function is useful for localizing faults that only occur when several lines are being operated concurrently from a single line card.
Stop all connections
All lines are detached. This is useful only in conjunction with 'Start all connections'.
Once this function has been executed, wait 15 seconds and then perform 'Start all connections'. This then corresponds to reading in all lines as they would appear on the line card in normal operation.