1. Launch the Climatix mobile app.
  2. Launch the mobile application to start with location services enabled on your smart phone or tablet.
  3. Plug in WLAN Stick into USB port in Controller.

NOTE: The Mobile application needs to start with location services enabled to determine the Climate Zone you are located in.
Once Climatix Mobile determines your location, you need to disable your location services and enable the Wi-Fi connection.

Connecting the WiFi:

  1. Select WiFi Settings
  2. Select Siemens-WLAN-Stick

WLAN Default Settings:

  • SSID: Siemens-WLAN-Stick
  • Password: SIBPAdmin

If password was changed and needs to be reset on WLAN stick:

Press and Hold for at least three seconds. A red flash LED signals the reset process.

Once the WiFi is connected, return to the Climatix App and select Continue.

Login to the controller for commissioning

 

The default Username is RTU

The default Password is SIBPAdmin!

The default PIN is: 6000

Select Connect.

NOTICE

We highly encourage to change the defaults in Climatix IC after the controller is connected and set-up is completed

For step-by-step instructions within the Mobile Application, see the Climatix RT Remote monitoring and Intelligent Diagnostics for Roof Top Unit Controllers Start-up (A6V12053407) for configuration options and screens