Multi-sensor fire detector OH731, OH731-S

The detectors have a sophisticated opto-electronic measuring chamber which contains one optical sensor and two thermal sensors. The optical sensor works with infra-red light at an average scattering angle of 90°.

Multi-criteria fire detector OOH751, OOH751-S

The detectors with ASAplus signal processing have a sophisticated opto-electronic measuring chamber which contains four optical sensors and two thermal sensors.

The optical sensors work as follows, at an average scattering angle:

  • Infra-red forward scatterer, 60°
  • Blue forward scatterer, 45°
  • Infra-red backward scatterer, 120°
  • Infra-red light, 90°

Smoke Entry Supervision

Smoke Entry Supervision is a dual-layer safety functionality built into the OH731-S and OOH751-S detectors. It ensures that smoke can reliably reach the sensing chamber by combining the following features:

  • Cover detection continuously checks whether the detector is not covered and provides live notification to the fire control panel and/or cloud if a covering object is detected.
  • Grid supervision continuously monitors the insect grid and notifies a user via fire control panel and/or cloud before the contamination level prevents smoke from reliably reaching the detection chamber.