Multi-sensor fire detector OH731, OH731-S
The detectors have a sophisticated opto-electronic measuring chamber which contains one optical sensor and two thermal sensors. The optical sensor works with infra-red light at an average scattering angle of 90°.
Multi-criteria fire detector OOH751, OOH751-S
The detectors with ASAplus signal processing have a sophisticated opto-electronic measuring chamber which contains four optical sensors and two thermal sensors.
The optical sensors work as follows, at an average scattering angle:
- Infra-red forward scatterer, 60°
- Blue forward scatterer, 45°
- Infra-red backward scatterer, 120°
- Infra-red light, 90°
Smoke Entry Supervision
Smoke Entry Supervision is a dual-layer safety functionality built into the OH731-S and OOH751-S detectors. It ensures that smoke can reliably reach the sensing chamber by combining the following features:
- Cover detection continuously checks whether the detector is not covered and provides live notification to the fire control panel and/or cloud if a covering object is detected.
- Grid supervision continuously monitors the insect grid and notifies a user via fire control panel and/or cloud before the contamination level prevents smoke from reliably reaching the detection chamber.