The OH731 and OH731-S detectors are designed for environments with low to moderate levels of deceptive phenomena.
The OOH751 and OOH751-S detectors are developed for detection in all environments, including complex and demanding conditions with high levels of deceptive phenomena or requiring quick response.
The following table contains examples of environments for selection of the fire detector and the parameter set.
Environment | Type Property | Parameter set |
|---|---|---|
Normal office, room without special deceptive phenomena | OH731/-S No special requirements | Standard |
Potential deceptive phenomena such as water boilers | OOH751/-S Steam as a deceptive phenomenon | Balanced Suppression |
Kitchen | OOH751/-S Large amounts of steam as a deceptive phenomenon | Suppression BS |
Hospital rooms, museum | OOH751/-S Quick response, no deceptive phenomena | Sensitive |
Clean rooms | OOH751/-S Quick and very sensitive response | Super Sensitive Ultra Sensitive |
Ventilation systems | OOH751/-S Quick and very sensitive response | Sensitive Super Sensitive |