The Commissioning Wizard and platform’s TCP/IP Configuration object configure controller TCP/IP settings. Workbench records TCP/IP before and after the change values in an ipchanges.bog file. If necessary, you can review these changes.
- Prerequisite: You are working in Workbench with a connection to the remote controller.
- Expand Platform and double-click TCP/IP Configuration.
- TCP/IP Configuration view opens.
- Click the Audit button.
- The ipchanges.bog folder’s AX Property Sheet opens.
Child folders are date-named with the format <yyyymmddhhmmss>, where the variable name contains year, month, day, hours, minutes, seconds; for example, d20250113153640 for 2025 Jan 13 3:36pm and 40 seconds. priorValue reports the TCP/IP settings that existed before the change. newValue reports the TCP/IP settings that existed after the change.
- Expand the folder and expand either priorValue or newValue. The included decoded modTime value is easier to read. For example, 13-Jan-2024 03:36 PM EST instead of d20150113153640).