After power-up, the thermostat resets and all LCD segments light up for about 3 seconds.

Wizard

After the first power-up, the device enters wizard mode and all commissioning parameters can be changed. After closing the wizard, the room temperature is displayed (factory setting).

Surge protection at power-up

When the thermostat is started up, the LCD display and key buttons work normally except all valve and fan outputs, e.g., Q1, Q2, Q3, Y1, and Y2.

The thermostat outputs start up at random to protect mains against overload. It may take a while before all outputs work properly.

Sensor calibration

The thermostat is equipped with an internal sensor for accurate temperature display. If the temperature display is influenced by its mounting location, calibrate the sensor via parameter P05 to adjust the readings.

Setpoint and range limitation

For comfort and to save energy, we suggest reviewing the setpoints (P11, P12, P65 and P66) and setpoint range (parameters P09 and P10) and change them as needed.

Other control parameters

The thermostat's control parameters can be adjusted to ensure optimum performance of the entire system (see “Control parameters”).