The building management system must be BTL certified for the following BACnet standardized device profiles:
- BACnet Cross-Domain Advanced Operator Workstation (B-XAWS)
- BACnet Advanced Operator Workstation (B-AWS)
- BACnet Advanced Life Safety Workstation (B-ALSWS)
- BACnet Advanced Access Control Workstation (B-AACWS)
- BACnet Router (B-RTR)
- BACnet Broadcast Management Device (B-BBMD)
They must also support BACnet data points and BACnet personal safety security zone functionality. The BACnet protocol revision must be at least 18.
The building management station must support seamless integration of alarming with BACnet devices, full support for commanding, writing and COVs to provide control and command functionality.
Finally, the system must support discovery and display of BACnet devices and all object types of BACnet protocol revision 18.
Specified products: Siemens / Desigo CC or similar