BACnet-based fire detection systems supporting BACnet BIBB AE-LS-B as well as objects LifeSafetyPoint and LifeSafetyZone as per the PICS (Protocol Implementation Conformance Statement) document must be able to be integrated for best deployment of a building automation and control system. The following functions must be supported:

  • Alarms and events from the fire detection system must be identified clearly and unambiguously.
  • Signaling device states must be displayed as per the BACnet standard.
  • Instruction texts must be able to be added to detectors and zones.
  • Situational and floor plans as well as dynamic symbols must be used for visualization.
  • A technical hierarchy, e.g. building, building part, zone, detector, must be provided to the operator for ease of operation.

Specified products: Siemens / Desigo System or similar