The system must be able to supply real time data from the management layer, as a BACnet/IP server, enabling communication and integration with third-party applications and systems, when necessary.
The following specifications must be met:
- The system must expose a system object as Analog, Binary and Multistate BACnet object
- The system must support of read, write and change of value (COV)
- The system must be able to expose management station trends as BACnet trend log objects
- The system must be able to expose BACnet alarms
- The system must be able to expose at least 20’000 objects per running server
A BACnet Protocol Implementation Conformance Statement (PICS) must also be available.
Specified products: Siemens / Desigo CC or similar