Alarms from the automation station must be displayed on the operator units within 1 second. Alarms must be acknowledged or acknowledged and reset dependent on access rights. Delay times (e.g. feedback supervision, triggering of differential pressure monitor, filter) must be changeable via operator units.

Specified products: Siemens / Desigo System or similar