The building management system must be implemented in accordance with the internationally recognized standards for industrial security ISA/IEC 62443, developed by the International Society of Automation (ISA) and adopted by the International Electrotechnical Commission (IEC).

  • The provider organization must have secure development processes certified to IEC 62443-4-1 Maturity Level 3 (ML3) or higher.
  • The building automation and control system must be certified to IEC 62443-4-2 Security Level 2 (SL2) or higher.

Specified products: Siemens / Desigo CC or similar