The system must allow the integration of power quality meters with the IEC61850 protocol.

In case a device generates a fault based on the waveform capture, the system must be able to download the file from the device for further analysis and storage.

The system must be able to visualize Power quality data in reports according to the EN 50160 standard.

Specified products:

  • Siemens / Desigo CC or similar
  • Siemens / SICAM Q100 Power Quality Recorder or similar
  • Siemens / SICAM Q200 Power Quality Recorder or similar