The EPMS must have reporting capabilities to process the acquired data.
The reporting engine must allow the scheduling of the report generation and emailing it as an attachment.
The following report templates must be available:
Load Duration
- Showing in Y axis the power and in X axis the time this power has been exceeded.
- Also showing the 50 highest reading in separate graph against the time of the day they occurred.
Top10
- Showing details about the top 10 energy consumers in the system.
Total Energy
- Showing the total energy consumption for selected points and period in Pie or Bar chart and compare across periods.
Standard
- Showing the readings in table format for the selected points from various devices.
Power Peak
- Showing the peak value per interval for a selected period against a predefined limit.
Load Variance
- Showing for the selected meter and time-period the power demand variation for all time intervals included in the period (overlay) as well as a separate graph the min, max and average values.
Energy Analysis
- Showing the Power demand for one whole year per month.
Cost Center
- Showing total energy and cost per cost center and medium with user definable cost per unit values.
Absolute Energy
- Showing the total energy consumption and its individual contributors in the stacked Bar or Area chart.
Sankey
- Showing the flow and distribution of energy
The system must be able to provide energy and power reports to visualize in addition:
- Load profiles
- Maximum power
- Energy consumption
- Comparison of consumptions
- Analysis of the data must be done at the local workstation and not in a cloud-based solution.
Specified products: Siemens / Desigo CC or similar