The EPMS must use libraries to allow the easy transfer of data from one project to another. (For example, object models of custom-made meters or custom-engineered graphics.
The EPMS must have pre-made object models and graphics for measuring devices and circuit breakers as well as dedicated graphics symbols for other commonly used electrical components such as batteries, switches and UPSs.
Specified products:
- Siemens / Desigo CC or similar
- Siemens / SENTRON Measuring Devices 7KT/7KM PAC or similar
- Siemens / SENTRON Circuit Breakers 3VA/3WA/3WL or similar
- Siemens / SENTRON Embedded Micro Metering Module SEM 3 or similar
- Siemens / SICAM Power Meters P850/P855 or similar
- Siemens / SICAM Q100 Power Quality Recorder or similar
- Siemens / SICAM Q200 Power Quality Recorder or similar