The Energy and Power Management (EPMS) must be capable of integrating any meter or circuit breaker that has a known Modbus registry map.

The EPMS must be capable of integrating all types of meters like heating, cooling, gas and water meters via protocols like Modbus, BACnet, OPC, SNMP, KNX.

The EPMS must allow the bulk import (integration) of many devices as well as import of individual devices.

The end user or engineer must be able to select for each meter or circuit breaker, which data points should be polled, displayed, and archived. Searching/filtering of the data point list must be available to help the process above be more efficient.

For each data point there must be the option to have a high or low limit that will create an alarm if exceeded.

The EPMS must allow the organization of integrated devices in Hierarchical structure with areas and sectors where the devices belong.

Specified products: Siemens / Desigo CC or similar