Energy and Power Management (EPMS) must be part of the Building Management System (BMS) software. More specifically:
- Operational and engineering data from EPMS must be in the same database as those of the BMS.
- The energy management system must be certified in accordance with ISO 50001 and thus meet the international standard for energy management systems.
- The following functions must use the same workflow, not requiring separate training or additional login:
- Trending
- Custom Graphics generation
- Alarms management
- Logs
- User management with various authorization levels
- Scripting
- Help
Specified products: Siemens / Desigo CC or similar