Providing calendar type formats to simplify time and data planning and override building operation is required. Time definitions must be located on the PC workstation and building controller to ensure scheduling even if the PC is offline.

Providing override access through menus, graphical mouse, of function keys. Providing the following operations at a minimum:

  • Comprehensive support of all BACnet objects for scheduler, calendar, and commands.
  • Daily and weekly schedules
  • Ability to compile multiple data points into a logical command group to simplify scheduling (e.g. Building 1 Lighting)
  • Planning predefined reports.
  • Ability to plan at least 10 years in advance.
  • Provide filters for schedulers by name, time, frequency, and schedule.
  • Provide sorting schedulers by name and schedule type.

Specified products: Siemens / Desigo CC or similar