The building management system must natively support Building Information Modeling (BIM) technology to perform the following actions:

  • Display visual and data information from Building Automation components such as room controllers, field devices etc., in a 3D view.
  • Display the 3D model of the building:
    • Allow operators to rotate, zoom in and zoom out the mode
    • Allow manual navigation through the 3D model, using the mouse cursor
    • Support simplified navigation with single mouse click to enter through doors, windows, and up/down staircases
    • Allow navigation from a system object via the browser to the associated equipment in the BIM view and vice versa
    • Allow selection of a BIM equipment and provide current (runtime) values and status properties. Commanding of objects shall be supported as well via the operating pane (such as switching on a light)
  • Display 2D floor plan(s) of the building
    • Show the selected room in focus (zoom view)
    • Show various rom statuses as colored carpets
    • Show current room values (runtime values) directly on the floor plan
    • Allow selection of a room or a segment
  • Display* room status in the 3D building view
    • Display the room operating mode (such as comfort, pre-comfort, etc.)
    • Display the presence detectors statuses
    • Display window states (open or closed) in a clear graphical format
    • Display the temperature status of a room
    • Display the lights’ state
    • Display the positioning state of the blinds
  • Provide a summary of all active events that are present on a selected area (such as a floor)
  • Show the location of the building in Google maps (where applicable)
  • Display the datasheet(s) and/or documentation of the selected equipment or field device, if relevant properties are present in the BIM data.
  • Supported Data formats:
    • IFC4
    • IFC2x3

* Optimized for Desigo Room Automation

Specified products: Siemens / Desigo CC or similar