PXC4.E16-2 variants 1)

PXC4.E16S-2

PXC4.E16-2

Order number

S55375-C152

S55375-C150

Number of inputs and outputs (Onboard)

16

16

     Number of universal inputs and outputs (UIO)

12

12

     Number of relay outputs (DO)

4

4

Number of inputs and outputs (Onboard + TXM)

up to 50

up to 50

Number of integration data points
(M-bus + Modbus TCP + Modbus RTU)

0

up to 40

Total number TXM-I/Os and integration DPs

50

90 2)

Number of KNX PL-Link devices

0

up to 64 2)

Number of configurable field level networks per RS485 (either for Modbus RTU or M-bus level converters with maximum of 250 meters each)

0

1

Number of M-bus meters wired via level converters (RS485) 3)

0

up to 250

Number of BACnet/SC nodes connected to PXC4.E16-2/PXC4.E16S-2 acting as hub

0
(node only)

0
(node only)

1) For details on engineering, see PXC4, PXC5 & PXC7 Planning overview (A6V13054435).

2) KNX PL-Link data points do not count as integration points. For KNX PL-Link, only the limits on BACnet objects are considered.

3) The limitation is given by the maximum number of integration data points and maximum number of BACnet objects.