The following table is designed to help you resolve issues while configuring and running the Building X Connector extension.

Problem

Cause

Resolution

The Agent Status in SMC for Building X Connector displays Stopped.

The Building Connect Agent is not running.

In SMC, select System, and then select the Building X Connector tab. From the Toolbar, click Start.

The Agent Status in SMC for Building X Connector displays Running, Disconnected

The Building Connect Agent is unable to communicate with Building X.

Check the network connection.

Make sure that you can log into the Building X organization.

The Agent Status in SMC for Building X Connector displays Running, Disconnected

The Building X Connector needs a proxy server to reach the internet.

See Setting up the Building X Connector to Work Behind a Proxy Server

The Agent Status in SMC for Building X Connector displays Running, Disconnected

If a proxy server is needed to connect to Building X, an activation key was created for the Building X Connector before the proxy server was configured

The activation key has incorrect file ownership and permissions. Make <proxyuser> the file owner and assign “Modify” rights

See the troubleshooting section Connecting via proxy if an activation key for the Building X Connector has already been generated .

The Agent Status in SMC for Building X Connector displays Running, Disconnected

The site is using a list of acceptable URLs and did not include the URL endpoints required to communicate to Building X.

Add the URL endpoints to the list of allowed URLs.

For more information, see the Desigo CC Cybersecurity Guidelines (A6V11646120).

In Desigo CC, the Operational State property displays Not Ready.

The Building Connect Agent is not running.

In the SMC Building X Connector tab, click Start.

In Desigo CC, the Operational State property displays Not Ready.

The Building Connect Agent ports are misconfigured.

Make sure configured ports are not conflicting with ports used by other applications on the Desigo CC server.

In Desigo CC, the Operational State property displays Not Ready.

No Building X Connector user is defined.

 

In Desigo CC, verify that a user account of the type Software account is defined and then configured in Building X Connector tab, Building X Connector Configuration expander, Software User drop-down.

In Desigo CC, the Operational State property displays Not Ready.

Unable to register Building X application

 

Make sure that the Building X site device and application is properly defined in the Building X Devices application.

In Desigo CC, the Operational State property displays Not Ready.

The application is not installed.

Make sure you complete all steps in Onboard the Management Station to Building X.

In Desigo CC, the Operational State property displays Not Ready.

The Desigo CC system account has been changed to use a specific account, and now the system does not have access to Building Connect agent configuration files.

Give the specific account used as the system account read privilege to the secrets folder, located here:

C:\ProgramData\Siemens\
IOT Cloud Connector\secrets

In Desigo CC, the Building X Data State property displays Data Not Aligned.

The Desigo CC configuration differs from the current Building X configuration.

Discover and Upload may be required in Desigo CC from the Building X Connector tab, Building X Preview Selection expander. Click Discover, and then click the Upload button.

In SMC, a previously configured Flex Client URL is not displaying.

There is a connectivity issue between the Building Connect Agent and Building X.

Resolve the connectivity issue, and then restart SMC to display the URL. If the URL still does not display, see Accessing Information in The Flex Client.

Alarms and COVs are not being sent to Building X.

In Desigo CC, the Indications State property is disabled.

In Extended Operation, locate the Indications State property, and then click Enable.

You do not see alarms in Building X.

Show is not selected for alarm categories in Event Rights.

Enable Show for alarm categories you want to view.

See Configuring the Building X Connector> Add a Security Group.

You do not see engineering units in Building X for some points that have been uploaded from Desigo CC

Conversion of units between Desigo CC and Building X is handled by a set of default mappings. If your Building X project is missing an engineering unit, you must update a custom mapping JSON file located within your project directory.

See the list of eligible Building X engineering units at GMSProjects\GMSMainProject\Data\BldgXConnector\QudtUnitsDescription.txt and a README file about changing the mappings at GMSProjects\GMSMainProject\Data\BldgXConnector\QudtUnitsDescriptionReadme.txt