This section provides procedures for configuring data point events in the Operations Manager app.

Only use this feature with data points that have no event behavior applied in their native field network or Edge application.

For all data points

  1. Select Launchpad > Operations Manager.
  1. From the multi-site Overview page, select a site.
  1. Go to one of the following:
  • Building hierarchy
  • Devices
  • The detected site tree displays.
  1. Expand the device that contains the data point you want to configure.
  • Next steps: depending on the data point type, do one of the following:

For two-state data points

  1. Select the data point.
  1. Under Event settings, do the following:
  • From the State drop-down menu, select an event state.
  • From the Category drop-down menu, select the appropriate event category.
  • Enable the configuration by switching the toggle button.
  • You have configured the event.

For high-low value data points

  1. Select the data point.
  1. Under Event settings, do the following:
  • In the Low limit field, enter a low limit value for the event, or use the up and down arrows.
  • In the High limit field, enter a value that is higher than the low limit, or use the up and down arrows.

    NOTE:
    If the value is equal to or less than the low limit value, the event configuration is disabled.
  • From the Category drop-down menu, select the appropriate event category.
  • Enable the configuration by switching the toggle button.
  • You have configured the event.

For multi-state data point

  1. Select the data point.
  1. Under Event settings, do the following:
  • From the State drop-down menu, select an event state.
  • From the Category drop-down menu, select the appropriate event category.
  • Enable the configuration by switching the toggle button.

    NOTE:
    If all or no states are selected, the Event settings section is in Read-Only mode and the toggle button cannot be enabled.
  • You have configured the event.