Hazardous pressure
Before pressurizing the system, make sure that all the valves are correctly mounted and secured.
Always assume that the discharge network and the selector valves are pressurized.
- Before any operation on the system, make sure that the system components are not pressurized.
- Ensure that the safety and protection equipment that is already in place has been properly mounted and commissioned.
- For safety reasons, the pneumatic drive must be pressurized gradually when used for the first time.
- When programming the ECP, ensure that the extinguishant cylinders associated to a protected zone cannot be activated before the actuation of the corresponding solenoid valve and selector valve.