Type | Name | English description | State 0 | State 1 |
|---|---|---|---|---|
DI | ET_LLL | Expansion Tank Low-low Level Status | OFF | ON |
DI | ET_LL | Expansion Tank Low Level Status | OFF | ON |
DI | ET_HL | Expansion Tank High Level Status | OFF | ON |
DI | ET_HHL | Expansion Tank High-high Level Status | OFF | ON |
DI | SM_LLL | Sump Low-low Level Status | OFF | ON |
DI | SM_LL | Sump Low Level Status | OFF | ON |
DI | SM_HL | Sump High Level Status | OFF | ON |
DI | SM_HHL | Sump High-high Level Status | OFF | ON |
DI | DWT_LLL | Domestic Water TankLow-low Level Status | OFF | ON |
DI | DWT_LL | Domestic Water TankLow Level Status | OFF | ON |
DI | DWT_HL | Domestic Water TankHigh Level Status | OFF | ON |
DI | DWT_HHL | Domestic Water TankHigh-high Level Status | OFF | ON |
DI | MT_LLL | Makeup Tank Low-low Level Status | OFF | ON |
DI | MT_LL | Makeup Tank Low Level Status | OFF | ON |
DI | MT_HL | Makeup Tank High Level Status | OFF | ON |
DI | MT_HHL | Makeup Tank High-high Level Status | OFF | ON |
DI | SWT_LLL | Soft Water Tank Low-low Level Status | OFF | ON |
DI | SWT_LL | Soft Water Tank Level Status | OFF | ON |
DI | SWT_HL | Soft Water Tank High Level Status | OFF | ON |
DI | SWT_HHL | Soft Water Tank High-high Level Status | OFF | ON |
DI | PMP_STA | Pump Status | OFF | ON |
DI | PMP_FA | Pump Fault Alarm | OK | FLT |
DI | PMP_MA | Pump Auto/Manual Select | MAN | AUTO |
DO | PMP_CMD | Pump Command | OFF | ON |
DI | SMP_STA | Sump Pump Status | OFF | ON |
DI | SMP_FA | Sump Pump Fault Alarm | OK | FLT |
DI | SMP_MA | Sump Pump Auto/Manual Select | MAN | AUTO |
DO | SMP_CMD | Sump Pump Command | OFF | ON |
DI | DWP_STA | Domestic Water Pump Status | OFF | ON |
DI | DWP_FA | Domestic Water Pump Fault Alarm | OK | FLT |
DI | DWP_MA | Domestic Water Pump Auto/Manual Select | MAN | AUTO |
DO | DWP_CMD | Domestic Water Pump Command | OFF | ON |
DI | MP_STA | Makeup Pump Status | OFF | ON |
DI | MP_FA | Makeup Pump Fault Alarm | OK | FLT |
DI | MP_MA | Makeup Pump Auto/Manual Select | MAN | AUTO |
DO | MP_CMD | Makeup Pump Command | OFF | ON |
DI | SWP_STA | Soft Water Pump Status | OFF | ON |
DI | SWP_FA | Soft Water Pump Fault Alarm | OK | FLT |
DI | SWP_MA | Soft Water Pump Auto/Manual Select | MAN | AUTO |
DO | SWP_CMD | Soft Water Pump Command | OFF | ON |
| ET | Expansion Tank |
|
|
| SM | Sump |
|
|
| DWT | Domestic Water Tank |
|
|
| MT | Makeup Tank |
|
|
| SWT | Soft Water Tank |
|
|
| PMP | Pump |
|
|
| SMP | Sump Pump |
|
|
| DWP | Domestic Water Pump |
|
|
| MP | Makeup Pump |
|
|
| SWP | Soft Water Pump |
|
|
| L | Level |
|
|
| LS | Level Status |
|
|
| LLL | Low-low Level Status |
|
|
| LLL_ALM | Low-low Level Alarm |
|
|
| LL | Low Level Status |
|
|
| HL | High Level Status |
|
|
| HHL | High-high Level Status |
|
|
| HHL_ALM | High-high Level Alarm |
|
|
| PSWP | Primary Supply Water Pressure |
|
|
| PRWP | Primary Return Water Pressure |
|
|
| PSWT | Primary Supply Water Temperature |
|
|
| PRWT | Primary Return Water Temperature |
|
|
| SSWP | Secondary Supply Water Pressure |
|
|
| SRWP | Secondary Return Water Pressure |
|
|
| SSWT | Secondary Supply Water Temperature |
|
|
| SRWT | Secondary Return Water Temperature |
|
|
| PVLV_CTL | Primary Valve Control |
|
|
| PCP | Primary Circulating Water Pump | OFF | ON |
| SCP | Secondary Circulating Water Pump | OFF | ON |
DI | PCP_STA | Primary Circulating Pump Status | OFF | ON |
DI | PCP_FA | Primary Circulating Pump Fault Alarm | OK | FLT |
DI | PCP_MA | Primary Circulating Pump Auto/Manual Select | MAN | AUTO |
DO | PCP_CMD | Primary Circulating Pump Command | OFF | ON |
DI | SCP_STA | Secondary Circulating Pump Status | OFF | ON |
DI | SCP_FA | Secondary Circulating Pump Fault Alarm | OK | FLT |
DI | SCP_MA | Secondary Circulating Pump Auto/Manual Select | MAN | AUTO |
DO | SCP_CMD | Secondary Circulating Pump Command | OFF | ON |