Type | Name | English description | Status/Unit | |
---|---|---|---|---|
BI | RAD_STA | Return Air Damper Status | OFF | ON |
BI | RAD_OS | Return Air Damper Open Status | OFF | OPN |
BI | RAD_CS | Return Air Damper Close Status | OFF | CLS |
BO | RAD_CMD | Return Air Damper Command | OFF | ON |
AI | RAD_FB | Return Air Damper Feedback | % | % |
AO | RAD_CTL | Return Air Damper Control | % | % |
BV | RAD_MOD | Return Air Damper Mode Select | MAN | AUTO |
AV | RAD_MSP | Return Air Damper Manual Setpoint | % | % |
AV | RAD_MIN | Return Air Damper Minimum Setpoint | % | % |
BI | MAD_STA | Mixed Air Damper Status | OFF | ON |
BI | MAD_OS | Mixed Air Damper Open Status | CLS | OPN |
BI | MAD_CS | Mixed Air Damper Close Status | OPN | CLS |
BO | MAD_CMD | Mixed Air Damper Command | OFF | ON |
AI | MAD_FB | Mixed Air Damper Feedback | % | % |
AO | MAD_CTL | Mixed Air Damper Control | % | % |
BV | MAD_MOD | Mixed Air Damper Mode Select | MAN | AUTO |
AV | MAD_MSP | Mixed Air Damper Manual Setpoint | % | % |
AV | MAD_MIN | Mixed Air Damper Minimum Setpoint | % | % |
BI | EAD_STA | Exhaust Air Damper Status | OFF | ON |
BI | EAD_OS | Exhaust Air Damper Open Status | CLS | OPN |
BI | EAD_CS | Exhaust Air Damper Close Status | OPN | CLS |
BO | EAD_CMD | Exhaust Air Damper Command | OFF | ON |
AI | EAD_FB | Exhaust Air Damper Feedback | % | % |
AO | EAD_CTL | Exhaust Air Damper Control | % | % |
BV | EAD_MOD | Exhaust Air Damper Mode Select | MAN | AUTO |
AV | EAD_MSP | Exhaust Air Damper Manual Setpoint | % | % |
AV | EAD_MIN | Exhaust Air Damper Minimum Setpoint | % | % |
BI | FILT_ALM | Filter Alarm | OK | FLT |
BI | PFILT_ALM | Primary Filter Alarm | OK | FLT |
BI | SFILT_ALM | Secondary Filter Alarm | OK | FLT |
BI | HFILT_ALM | Hepa Filter Alarm | OK | FLT |
BI | RFILT_ALM | Return Filter Alarm | OK | FLT |
BI | LLT_ALM | Low limit Temperature Alarm | OK | FLT |
BV | WS_MOD | Winter_Summer Mode Select | SUMMER | WINTER |
BV | ECON_ENA | Economic Model /Spring and Autumn Seasons Model | OFF | ON |
BV | SCH_MOD | Schedule Mode Select | RemMAN | Schedule |
BV | AHU_SS | AHU Start/Stop | OFF | ON |
CE | AHU_MOD | AHU Mode Select | MAN | GROUP |
DO | ALM_LED | Alarm LED | OK | FLT |
BV | OAD_MOD | Outside Air Damper Tunning Mode | PRESET | PID |
AV | OAD_SP | Outside Air Damper Pre-set Setpoint | % | % |
BV | OAT_FLT | Outside Air Temperature Sensor Fault | OK | FLT |
BV | RAT_FLT | Return Air Temperature Sensor Fault | OK | FLT |
BV | SAT_FLT | Supply Air Temperature Sensor Fault | OK | FLT |
BV | RMT_FLT | Room Air Temperature Sensor Fault | OK | FLT |