Type | Name | English description | Status/Unit | |
---|---|---|---|---|
AI | RMT | Room Temperature | °C | °C |
AV | RMT_SP | Room Temperature Setpoint | °C | °C |
AI | RMH | Room Humidity | %RH | %RH |
AV | RMH_SP | Room Humidity Setpoint | %RH | %RH |
AI | RMP | Room Pressure | Pa | Pa |
AV | RMP_SP | Room Pressure Setpoint | Pa | Pa |
AI | RM_DP | Room Differential Pressure | Pa | Pa |
AV | RM_DPSP | Room Differential Pressure Setpoint | Pa | Pa |
AI | RM_CO2 | Room CO2 Level | ppm | ppm |
AV | RM_CO2SP | Room CO2 Level Setpoint | ppm | ppm |
AI | RM_CO | Room CO Level | ppm | ppm |
AV | RM_COSP | Room CO Level Setpoint | ppm | ppm |
AV | RM_ENT | Room Enthalpy | kJ/kg | kJ/kg |
AI | RAT | Return Air Temperature | °C | °C |
AV | RAT_SP | Return Air Temperature Setpoint | °C | °C |
AI | RAH | Return Air Humidity | %RH | %RH |
AV | RAH_SP | Return Air Humidity Setpoint | %RH | %RH |
AI | RA_SP | Return Air Static Pressure | Pa | Pa |
AI | RA_CO2 | Return Air CO2 Level | ppm | ppm |
AV | RA_CO2SP | Return Air CO2 Level Setpoint | ppm | ppm |
AI | RA_CO | Return Air CO Level | ppm | ppm |
AV | RA_COSP | Return Air CO Level Setpoint | ppm | ppm |
AI | RA_FLOW | Return Air Flow Rate | l/s, m3/h | l/s, m3/h |
AV | RA_FLSP | Return Air Flow Rate Setpoint | l/s, m3/h | l/s, m3/h |
AV | RA_ENT | Return Air Enthalpy | kJ/kg | kJ/kg |
AI | EAT | Exhaust Air Temperature | °C | °C |
AI | EAH | Exhaust Air Humidity | %RH | %RH |
AI | EA_SP | Exhaust Air Static Pressure | Pa | Pa |
AV | EA_SPSP | Exhaust Air Static Pressure Setpoint | Pa | Pa |
AI | EA_FLOW | Exhaust Air Flow Rate | l/s, m3/h | l/s, m3/h |
AV | EA_FLSP | Exhaust Air Flow Rate Setpoint | l/s, m3/h | l/s, m3/h |
AI | DEWT | Dew Point Temperature | °C | °C |
AV | DEWT_SP | Dew Point Temperature Setpoint | °C | °C |
AI | SA_DEWT | Supply Air Dew Point Temperature | °C | °C |
AV | SA_DEWTSP | Supply Air Dew Point Temperature Setpoint | °C | °C |
AI | COIL_DT | Coil Downstream Temperature | °C | °C |
AV | COIL_DTSP | Coil Downstream Temperature Setpoint | °C | °C |
AI | CCOIL_DT | Cooling Coil Downstream Temperature | °C | °C |
AV | CCOIL_DTSP | Cooling Coil Downstream Temperature Setpoint | °C | °C |
AI | HCOIL_DT | Heating Coil Downstream Temperature | °C | °C |
AV | HCOIL_DTSP | Heating Coil Downstream Temperature Setpoint | °C | °C |
AI | VLV_FB | Cooling/Heating Valve feedback | % | % |
AO | VLV_CTL | Cooling/Heating Valve Control | % | % |
BV | VLV_MOD | Cooling/Heating Valve Mode Select | MAN | AUTO |
AV | VLV_MSP | Cooling/Heating Valve Manual Setpoint | % | % |
AV | VLV_MIN | Cooling/Heating Valve Minimum Setpoint | % | % |
AI | CV_FB | Cooling Valve Feedback | % | % |
AO | CV_CTL | Cooling Valve Control | % | % |
BV | CV_MOD | Cooling Valve Mode Select | MAN | AUTO |
AV | CV_MSP | Cooling Valve Manual Setpoint | % | % |
AV | CV_MIN | Cooling Valve Minimum Setpoint | % | % |
AI | HV_FB | Heating Valve Feedback | % | % |
AO | HV_CTL | Heating Valve Control | % | % |
BV | HV_MOD | Heating Valve Mode Select | MAN | AUTO |
AV | HV_MSP | Heating Valve Manual Setpoint | % | % |
AV | HV_MIN | Heating Valve Minimum Setpoint | % | % |
DO | HUM_CMD | Humidifier Command | OFF | ON |
AO | HUM_CTL | Humidifier Control | % | % |
BV | HUM_MOD | Humidifier Mode Select | MAN | AUTO |
AV | HUM_MSP | Humidifier Manual Setpoint | % | % |
AV | HUM_MIN | Humidifier Minimum Setpoint | % | % |
BI | EH_STA | Electric Heater Status | OFF | ON |
BI | EH_MA | Electric Heater Auto/Manual Select | MAN | AUTO |
BI | EH_FA | Electric Heater Fault Alarm | OK | FLT |
BO | EH_CMD | Electric Heater Command | OFF | ON |
BI | OAD_STA | Outside Air Damper Status | OFF | ON |
BI | OAD_OS | Outside Air Damper Open Status | OPN | OPN |
BI | OAD_CS | Outside Air Damper Close Status | CLS | CLS |
BO | OAD_CMD | Outside Air Damper Command | OFF | ON |
AI | OAD_FB | Outside Air Damper Feedback | % | % |
AO | OAD_CTL | Outside Air Damper Control | % | % |
BV | OAD_MOD | Outside Air Damper Mode Select | MAN | AUTO |
AV | OAD_MSP | Outside Air Damper Manual Setpoint | % | % |
AV | OAD_MIN | Outside Air Damper Minimum Setpoint | % | % |
BI | SAD_STA | Supply Air Damper Status | OFF | ON |
BI | SAD_OS | Supply Air Damper Open Status | OFF | OPN |
BI | SAD_CS | Supply Air Damper Close Status | OFF | CLS |
BO | SAD_CMD | Supply Air Damper Command | OFF | ON |
AI | SAD_FB | Supply Air Damper Feedback | % | % |
AO | SAD_CTL | Supply Air Damper Control | % | % |
BV | SAD_MOD | Supply Air Damper Mode Select | MAN | AUTO |
AV | SAD_MSP | Supply Air Damper Manual Setpoint | % | % |
AV | SAD_MIN | Supply Air Damper Minimum Setpoint | % | % |