Unit Start/Stop can be set to OFF after the valve output (AO) has reached 10 V in the above scenario. The primary valve output (AO) is closed from 10 to 0 V immediately. The circulating pump output (DO) is switched off after a delay of 60 seconds.
Unit Start/Stop can be set to OFF after the valve output (AO) has reached 10 V in the above scenario. The primary valve output (AO) is closed from 10 to 0 V immediately. The circulating pump output (DO) is switched off after a delay of 60 seconds.