Alarm# | Alarm description | Reset type | Alarm source | Action accordingly |
---|---|---|---|---|
001 | Secondary Supply Water Pressure High Alarm | Automatic | AI analog Alarms if the secondary supply water pressure is higher than the setpoint after Unit Start/Stop is ON | Stops the unit |
002 | Secondary Supply Water Pressure Low Alarm | Automatic | AI analog Alarms if the secondary return water pressure is lower than the setpoint after Unit Start/Stop is ON | Stops the unit |
003 | Circulating Pump Fault Alarm | Automatic | DI Switch Closes when alarm comes, opens when alarm goes | Stops the unit |
004 | Makeup Pump Fault Alarm | Automatic | DI Switch Closes when alarm comes, opens when alarm goes | Stops the unit |