Start condition: When Unit Start/Stop is ON.
Stop condition: Stop if any of the following conditions are met:
- After Unit Start/Stop is OFF for 60 seconds.
- The unit reports a critical failure alarm.
- Secondary supply water pressure is high (e.g., over 6 bar).
- Secondary return water pressure is low (e.g., below 0.5 bar).