No. | Name | Description | R/W | Data type | Default value and range |
---|---|---|---|---|---|
1 | UNIT_SS | Unit Start/Stop | R/W | BOOL | 0 (default), 0-OFF / 1-ON |
2 | SSW_P_HI_ALM | Secondary Supply Water Pressure High Alarm | R | BOOL | 0 (default), 0-OK / 1-FLT |
3 | SRW_P_LO_ALM | Secondary Supply Water Pressure Low Alarm | R | BOOL | 0 (default), 0-OK / 1-FLT |
4 | CP_OFF_SWP_SP | Circulating Water Pump Shut-down Supply Water Pressure Setpoint | R/W | FLOAT | 6 (default), 0...20 bar |
5 | CP_OFF_RWP_SP | Circulating Water Pump Shut-down Return Water Pressure Setpoint | R/W | FLOAT | 0.5 (default), 0...20 bar |
6 | MP_OFF_RWP_SP | Makeup Pump Shut-down Return Water Pressure Setpoint | R/W | FLOAT | 4 (default), 0...20 bar |
7 | MP_ON_RWP_SP | Makeup Pump Start-up Return Water Pressure Setpoint | R/W | FLOAT | 2.5 (default), 0...20 bar |
8 | SSW_TSP | Secondary Supply Water Temperature Setpoint | R/W | FLOAT | 50 (default), 10...100 °C |
9 | GEN_ALM | General Alarm | R | BOOL | 0-OK / 1-FLT |
10 | ALM_STOP | Alarm Stop | R | BOOL | 0-OK / 1-FLT |
11 | ALM_RST | Alarm Reset Pulse | R/W | BOOL | 0 (default), 0-OFF / 1-RST |