This template is used to control a simple two-pipe air conditioning unit with return fan. The two operating modes it supports, heating in winter and cooling in summer, are selectable via "Winter_Summer Mode Select". Outside Air Damper Control generates outputs based on preset values, return air CO2 level and PID calculation, while Heating/Cooling Valve Control generates outputs based on return air temperature, temperature setpoint and PID calculation. Fault Alarm Protection includes individual sensor fault alarms, filter differential pressure switch and low limit temperature switch.

Legend

Description

Legend

Description

OAT

Outside Air Temperature

SF

Supply Fan

RAD

Return Air Damper

SAT

Supply Air Temperature

OAD

Outside Air Damper

RAT

Return Air Temperature

FILT

FILTER

RACO2

Return Air CO2

LLT

Low Limit Temperature

R

Room

VLV

Valve