This template is used to control a two-pipe fresh air unit. The two operating modes it supports, heating in winter and cooling in summer, are selectable via "Winter_Summer Mode Select". Heating/Cooling Valve Control generates PID-calculated outputs based on the supply air temperature value and setpoint. Fault Alarm Protection includes individual sensor fault alarms, filter differential pressure switch and low limit temperature switch.
Legend | Description | Legend | Description |
---|---|---|---|
OAT | Outside Air Temperature | VLV | Valve |
OAD | Outside Air Damper | SF | Supply Fan |
FILT | FILTER | SAT | Supply Air Temperature |
LLT | Low Limit Temperature |