No.

Name

Description

R/W

Data type

Default value and range

1

SM_LLL_ALM

Sump Low-low Level Status Alarm

R

BOOL

0-OK / 1-FLT

2

SM_HHL_ALM

Sump High-high Level Status Alarm

R

BOOL

0-OK / 1-FLT

3

SMP_HRS1

Sump Operation Hour 1

R

FLOAT

0...65535 h

4

SMP_HRS2

Sump Operation Hour 2

R

FLOAT

0...65535 h

5

CLR_SMP_HRS1

Sump Operation Hour Clear-off 1

R/W

BOOL

0-OFF / 1-RST

6

CLR_SMP_HRS2

Sump Operation Hour Clear-off 2

R/W

BOOL

0-OFF / 1-RST

7

UNIT_SS

Unit Start/Stop

R/W

BOOL

0-OFF / 1-ON

8

SMP_ROT_CMD

Sump Pump Rotation Command

R/W

BOOL

0-OFF / 1-ON

9

SMP_ROT_HRS

Sump Pump Rotation Hours

R/W

FLOAT

10 (default), 0...65535 h

10

PP_GEN_CMD

Periodic Pulse Generation Command

R/W

BOOL

0-OPN / 1-CLS

11

ALM_RST

Alarm Reset Pulse

R/W

BOOL

0 (default), 0-OFF / 1-RST

12

GEN_ALM

General Alarm

R/W

BOOL

0-OK / 1-FLT

13

ALM_STOP

Alarm Stop

R

BOOL

0-OK / 1-FLT

14

HL_FILTER

High Level Filtering

R/W

BOOL

0-OFF / 1-ON