Start condition: When Unit Start/Stop is ON and no shutdown condition exists, Outside Air Damper Control is Outside Air Damper Pre-set Setpoint if PRESET is selected. If PID is selected, the control is driven by corresponding PID settings such as return air CO2 current level and setpoint.

Stop condition: 30 seconds after Unit Start/Stop is set to OFF and the fan is switched off.