No. | Name | Description | R/W | Data type | Default value and range |
---|---|---|---|---|---|
1 | OAD_SP | Outside Air Damper Pre-set Setpoint | R/W | FLOAT | 15 (default), 0...60 % |
2 | RAT_SP | Return Air Temperature Setpoint | R/W | FLOAT | 23 (default), 10...40 °C |
3 | CLG_KP | Cooling Scale Factor | R/W | FLOAT | 10 (default), 0...100 |
4 | CLG_TI | Cooling Integral Time | R/W | FLOAT | 120 (default), 0...300 |
5 | HTG_KP | Heating Scale Factor | R/W | FLOAT | 10 (default), 0...100 |
6 | HTG_TI | Heating Integral Time | R/W | FLOAT | 120 (default), 0...300 |
7 | WS_MOD | Winter_Summer Mode Select | R/W | BOOL | 0 (default), 0-WIN / 1-SUM |
8 | RA_CO2SP | Return Air CO2 Level Setpoint | R/W | FLOAT | 400 (default), 0...2000 ppm |
9 | OAD_MIN | Outside Air Damper Minimum Setpoint | R/W | FLOAT | 30 (default), 0...100 % |
10 | FILT_ALM | Filter Alarm | R | BOOL | 0-OK / 1-FLT |
11 | GEN_ALM | General Alarm | R | BOOL | 0-OK / 1-FLT |
12 | ALM_STOP | Alarm Stop | R | BOOL | 0-OK / 1-FLT |
13 | ALM_RST | Alarm Reset Pulse | R/W | BOOL | 0 (default), 0-OFF / 1-RST |
14 | OAT_FLT | Outside Air Temperature Sensor Fault | R | BOOL | 0-OK / 1-FLT |
15 | SAT_FLT | Supply Air Temperature Sensor Fault | R | BOOL | 0-OK / 1-FLT |
16 | RAT_FLT | Return Air Temperature Sensor Fault | R | BOOL | 0-OK / 1-FLT |
17 | RA_CO2_FLT | Return Air CO2 Sensor Fault | R | BOOL | 0-OK / 1-FLT |
18 | LLT_ALM | Low limit Temperature Alarm | R | BOOL | 0-OK / 1-FLT |
19 | FAN_FLT | Fan Fault Alarm | R | BOOL | 0-OK / 1-FLT |
20 | FAN_DP_ALM | Fan Differential Pressure Alarm | R | BOOL | 0-OK / 1-FLT |
21 | UNIT_SS | Unit Start/Stop | R/W | BOOL | 0 (default), 0-OFF / 1-ON |