No.

Name

Description

R/W

Data type

Default value and range

1

OAD_SP

Outside Air Damper Pre-set Setpoint

R/W

FLOAT

15 (default), 0...60 %

2

RAT_SP

Return Air Temperature Setpoint

R/W

FLOAT

23 (default), 10...40 °C

3

CLG_KP

Cooling Scale Factor

R/W

FLOAT

10 (default), 0...100

4

CLG_TI

Cooling Integral Time

R/W

FLOAT

120 (default), 0...300

5

HTG_KP

Heating Scale Factor

R/W

FLOAT

10 (default), 0...100

6

HTG_TI

Heating Integral Time

R/W

FLOAT

120 (default), 0...300

7

WS_MOD

Winter_Summer Mode Select

R/W

BOOL

0 (default), 0-WIN / 1-SUM

8

RA_CO2SP

Return Air CO2 Level Setpoint

R/W

FLOAT

400 (default), 0...2000 ppm

9

OAD_MIN

Outside Air Damper Minimum Setpoint

R/W

FLOAT

30 (default), 0...100 %

10

FILT_ALM

Filter Alarm

R

BOOL

0-OK / 1-FLT

11

GEN_ALM

General Alarm

R

BOOL

0-OK / 1-FLT

12

ALM_STOP

Alarm Stop

R

BOOL

0-OK / 1-FLT

13

ALM_RST

Alarm Reset Pulse

R/W

BOOL

0 (default), 0-OFF / 1-RST

14

OAT_FLT

Outside Air Temperature Sensor Fault

R

BOOL

0-OK / 1-FLT

15

SAT_FLT

Supply Air Temperature Sensor Fault

R

BOOL

0-OK / 1-FLT

16

RAT_FLT

Return Air Temperature Sensor Fault

R

BOOL

0-OK / 1-FLT

17

RA_CO2_FLT

Return Air CO2 Sensor Fault

R

BOOL

0-OK / 1-FLT

18

LLT_ALM

Low limit Temperature Alarm

R

BOOL

0-OK / 1-FLT

19

FAN_FLT

Fan Fault Alarm

R

BOOL

0-OK / 1-FLT

20

FAN_DP_ALM

Fan Differential Pressure Alarm

R

BOOL

0-OK / 1-FLT

21

UNIT_SS

Unit Start/Stop

R/W

BOOL

0 (default), 0-OFF / 1-ON