No.

Name

Description

R/W

Data type

Default value and range

1

UNIT_SS

Unit Start/Stop

R/W

BOOL

0 (default), 0-OFF / 1-ON

2

FAN_VFD_MOD

Fan Variable Frequency Drive Mode Select

R/W

BOOL

0-MAN / 1-AUTO

3

OAD_SP

Outside Air Damper Pre-set Setpoint

R/W

FLOAT

15 (default), 0...60 %

4

RAT_SP

Return Air Temperature Setpoint

R/W

FLOAT

20 (default), 10...40 °C

5

RAH_SP

Return Air Humidity Setpoint

R/W

FLOAT

50 (default), 10...60 %

6

SA_SPSP

Supply Air Static Pressure Setpoint

R/W

FLOAT

500 (default), 0...1000 Pa

7

RA_CO2SP

Return Air CO2 Level Setpoint

R/W

FLOAT

500 (default), 0...2000 ppm

8

CLG_KP

Cooling Scale Factor

R/W

FLOAT

10 (default), 0...100

9

CLG_TI

Cooling Integral Time

R/W

FLOAT

120 (default), 0...300

10

HTG_KP

Heating Scale Factor

R/W

FLOAT

10 (default), 0...100

11

HTG_TI

Heating Integral Time

R/W

FLOAT

120 (default), 0...300

12

PFILT_ALM

Primary Filter Alarm

R

BOOL

0-OK / 1-FLT

13

SFILT_ALM

Secondary Filter Alarm

R

BOOL

0-OK / 1-FLT

14

VFD_KP

VFD Fan Scale Factor

R/W

FLOAT

10 (default), 0...100

15

VFD_TI

VFD Fan Integral Time

R/W

FLOAT

120 (default), 0...300

16

OAD_MOD

Outside Air Damper Mode Select

R/W

BOOL

0-MAN / 1-AUTO

17

EAD_MOD

Exhaust Air Damper Mode Select

R/W

BOOL

0-MAN / 1-AUTO

18

MAD_MOD

Mixed Air Damper Mode Select

R/W

BOOL

0-MAN / 1-AUTO

19

MAD_MSP

Mixed Air Damper Manual Setpoint

R/W

FLOAT

0 (default), 0...100 %

20

EAD_MSP

Exhaust Air Damper Manual Setpoint

R/W

FLOAT

0 (default), 0...100 %

21

OAD_MSP

Outside Air Damper Manual Setpoint

R/W

FLOAT

0 (default), 0...100 %

22

LLT_ALM

Low limit Temperature Alarm

R

BOOL

0-OK / 1-FLT

23

OAT_FLT

Outside Air Temperature Sensor Fault

R

BOOL

0-OK / 1-FLT

24

OAH_FLT

Outside Air Humidity Sensor Fault

R

BOOL

0-OK / 1-FLT

25

SAH_FLT

Supply Air Humidity Sensor Fault

R

BOOL

0-OK / 1-FLT

26

SAT_FLT

Supply Air Temperature Sensor Fault

R

BOOL

0-OK / 1-FLT

27

RAT_FLT

Return Air Temperature Sensor Fault

R

BOOL

0-OK / 1-FLT

28

RAH_FLT

Return Air Humidity Sensor Fault

R

BOOL

0-OK / 1-FLT

29

RA_CO2_FLT

Return Air CO2 Sensor Fault

R

BOOL

0-OK / 1-FLT

30

SA_SP_FLT

Supply Air Static Pressure Sensor Fault

R

BOOL

0-OK / 1-FLT

31

GEN_ALM

General Alarm

R

BOOL

0-OK / 1-FLT

32

ALM_STOP

Alarm Stop

R

BOOL

0-OK / 1-FLT

33

ALM_RST

Alarm Reset Pulse

R/W

BOOL

0 (default), 0-OFF / 1-RST

34

SF_DP_ALM

Supply Fan Differential Pressure Alarm

R

BOOL

0-OK / 1-FLT

35

RF_DP_ALM

Return Fan Differential Pressure Alarm

R

BOOL

0-OK / 1-FLT

36

DEHU_KP

Dehumidification Scale Factor

R/W

FLOAT

10 (default), 0...100

37

DEHU_TI

Dehumidification Integral Time

R/W

FLOAT

120 (default), 0...300