No. | Name | Description | R/W | Data type | Default value and range |
---|---|---|---|---|---|
1 | UNIT_SS | Unit Start/Stop | R/W | BOOL | 0 (default), 0-OFF / 1-ON |
2 | FAN_VFD_MOD | Fan Variable Frequency Drive Mode Select | R/W | BOOL | 0-MAN / 1-AUTO |
3 | OAD_SP | Outside Air Damper Pre-set Setpoint | R/W | FLOAT | 15 (default), 0...60 % |
4 | RAT_SP | Return Air Temperature Setpoint | R/W | FLOAT | 20 (default), 10...40 °C |
5 | RAH_SP | Return Air Humidity Setpoint | R/W | FLOAT | 50 (default), 10...60 % |
6 | SA_SPSP | Supply Air Static Pressure Setpoint | R/W | FLOAT | 500 (default), 0...1000 Pa |
7 | RA_CO2SP | Return Air CO2 Level Setpoint | R/W | FLOAT | 500 (default), 0...2000 ppm |
8 | CLG_KP | Cooling Scale Factor | R/W | FLOAT | 10 (default), 0...100 |
9 | CLG_TI | Cooling Integral Time | R/W | FLOAT | 120 (default), 0...300 |
10 | HTG_KP | Heating Scale Factor | R/W | FLOAT | 10 (default), 0...100 |
11 | HTG_TI | Heating Integral Time | R/W | FLOAT | 120 (default), 0...300 |
12 | PFILT_ALM | Primary Filter Alarm | R | BOOL | 0-OK / 1-FLT |
13 | SFILT_ALM | Secondary Filter Alarm | R | BOOL | 0-OK / 1-FLT |
14 | VFD_KP | VFD Fan Scale Factor | R/W | FLOAT | 10 (default), 0...100 |
15 | VFD_TI | VFD Fan Integral Time | R/W | FLOAT | 120 (default), 0...300 |
16 | OAD_MOD | Outside Air Damper Mode Select | R/W | BOOL | 0-MAN / 1-AUTO |
17 | EAD_MOD | Exhaust Air Damper Mode Select | R/W | BOOL | 0-MAN / 1-AUTO |
18 | MAD_MOD | Mixed Air Damper Mode Select | R/W | BOOL | 0-MAN / 1-AUTO |
19 | MAD_MSP | Mixed Air Damper Manual Setpoint | R/W | FLOAT | 0 (default), 0...100 % |
20 | EAD_MSP | Exhaust Air Damper Manual Setpoint | R/W | FLOAT | 0 (default), 0...100 % |
21 | OAD_MSP | Outside Air Damper Manual Setpoint | R/W | FLOAT | 0 (default), 0...100 % |
22 | LLT_ALM | Low limit Temperature Alarm | R | BOOL | 0-OK / 1-FLT |
23 | OAT_FLT | Outside Air Temperature Sensor Fault | R | BOOL | 0-OK / 1-FLT |
24 | OAH_FLT | Outside Air Humidity Sensor Fault | R | BOOL | 0-OK / 1-FLT |
25 | SAH_FLT | Supply Air Humidity Sensor Fault | R | BOOL | 0-OK / 1-FLT |
26 | SAT_FLT | Supply Air Temperature Sensor Fault | R | BOOL | 0-OK / 1-FLT |
27 | RAT_FLT | Return Air Temperature Sensor Fault | R | BOOL | 0-OK / 1-FLT |
28 | RAH_FLT | Return Air Humidity Sensor Fault | R | BOOL | 0-OK / 1-FLT |
29 | RA_CO2_FLT | Return Air CO2 Sensor Fault | R | BOOL | 0-OK / 1-FLT |
30 | SA_SP_FLT | Supply Air Static Pressure Sensor Fault | R | BOOL | 0-OK / 1-FLT |
31 | GEN_ALM | General Alarm | R | BOOL | 0-OK / 1-FLT |
32 | ALM_STOP | Alarm Stop | R | BOOL | 0-OK / 1-FLT |
33 | ALM_RST | Alarm Reset Pulse | R/W | BOOL | 0 (default), 0-OFF / 1-RST |
34 | SF_DP_ALM | Supply Fan Differential Pressure Alarm | R | BOOL | 0-OK / 1-FLT |
35 | RF_DP_ALM | Return Fan Differential Pressure Alarm | R | BOOL | 0-OK / 1-FLT |
36 | DEHU_KP | Dehumidification Scale Factor | R/W | FLOAT | 10 (default), 0...100 |